Skip to content
English
  • There are no suggestions because the search field is empty.

USA Lab Proper Chiller Operation

This guide outlines the three required steps for proper chiller operation: waiting period before use, approved coolant selection, and priming the water pump. Failure to follow these steps will void the warranty.

Link to USA Lab Chiller Operating Warning


Quick Facts

  • Mandatory Wait Time: 12 hours
  • Coolant Requirements: Distilled water–based glycol
  • Maximum Glycol Concentration: 50%
  • Pump Priming: Required before operation
  • Warranty Note: Damage caused by ignoring these steps voids warranty

STEP 1 — Wait 12 Hours Before Use

  • The compressor oil may migrate out of the compressor and into the refrigerant lines.
  • If the chiller is operated immediately, the compressor may run without sufficient oil, causing damage.
  • A full 12-hour wait time is required before powering on the chiller.

STEP 2 — Use a Distilled Water–Based Glycol Antifreeze

  • Use distilled water–based glycol antifreeze only.
  • Glycol concentration must be no more than 50%.
  • Do NOT use automotive antifreeze — its additives are known to corrode heat exchangers.
  • Do NOT use tap water — it can cause rusting of internal parts.
  • Dynalene HC is acceptable.

STEP 3 — Prime the Water Pump Before Use

  • Use a short length of tubing (about 2 feet long).
  • Connect the outlet and inlet together.
  • Run the pump until no bubbles appear in the water line.
  • Shut down the pump.
  • Close the outlet valve.
  • The pump is now properly primed.

Warranty Warning

  • Any damage caused by not following these steps will void the warranty.

Contact & Support

For chiller setup questions or coolant recommendations:

📞 734-855-4890
📧 support@usalabequipment.com